FBs Series > Temperature Measurement Expansion Modules
Thermocouple modules |
Model number \ Specification |
|||
![]() |
Number of input points |
2 points |
6 points |
16 points |
Thermocouple type and temperature measurement range |
J(-200~900°C) E(-190~1000°C) K(-190~1300°C) T(-190~380°C) R(0~1800°C) B(350~1800°C) S(0~1700°C) N(-200~1000°C) |
|||
Temperature compensation |
Built-in cold junction compensation |
|||
Resolution |
0.1°C |
|||
Temperature refresh time |
1 or 2 seconds |
2 or 4 seconds |
3 or 6 seconds |
|
Overall Precision |
±1% |
|||
Isolation method |
Transformer (power) and photocouple (signal) isolation (per-channel isolation) |
|||
Power input |
24VDC-15%/+20%、2VA max |
|||
RTD modules |
Model number \ Specification |
||
![]() |
Number of input points | 6points |
16points |
| RTD type and temperature measurement range |
3-wire RTD sensor (JIS or DIN) Pt-100(-200~850°C) Pt-1000(-200~600°C) |
||
| Resolution | 0.1°C |
||
| Temperature refresh time | 1 or 2 seconds |
2 or 4 seconds |
|
| Overall Precision |
±1% |
||
| Isolation method | Transformer (power) and photocouple (signal) isolation (no isolation between channels) |
||
| Power input | 24VDC-15%/+20%、2VA max |
||