FBs Series >Temperature Measurement Module

 

 

Spec

Model

FBs-TC2

FBs-TC6

FBs-TC16

FBs-RTD6

FBs-RTD16

FBs-NTC6

Number of input points

2 points

6 points

16 points

6 points

16 points

6 points

Sensor type and temperature measurement range

Thermocouple Sensor:
J (-200~1200°C) E(-190~1000°C)
K (-190~1300°C) T(-190~380°C )
R (0~1800°C ) B( 350~1800°C)
S (0~1700°C ) N(-200~1000°C)

3-wire RTD sensor (JIS or DIN)
Pt100(-200°C~850°C)
Pt1000(-200°C~600°C)

NTC sensor
10 KΩ at 25°C, B optional
-20°C ~ 100°C

Temperature compensation

Built-in cold junction compensation

Resolution

0.1°C

Temperature refresh time

1 or 2 seconds

2 or 4 seconds

3 or 6 seconds

1 or 2 seconds

2 or 4 seconds

2 or 4 seconds

Overall Precision

± (1%+1°C)

± 1%

+/- 1 % of full scale at 25°C

Isolation method

Transformer (power) and photocouple (signal) isolation

Power consumption

24VDC -15%/+20%,2VA max.

Wiring mechanism

3.81 mm European terminal block

7.62 mm terminal block

 